Siemens 8DJH Switchgear cable current transformer Features

  • Accordingto IEC / EN 61869-1 and -2 / VDE 0414-9-1 and -2
  • Designed asring-core current transformers, 1-pole
  • Free of dielectrically stressed cast-resin parts (due to design)
  • Insulation classE
  • Inductive type
  • Secondaryconnection by means of a terminal strip  in the panel.

Siemens 8DJH Switchgear cable current transformer Installation

The mounting location is out- side the switchgear vessel,around the cable at the panel connection; installation on the cable on site.

Note: Installation inside or underneath the panel depend- ing on the panel type and the overall transformer height.

Three-phase current transformer:

Siemens 8DJH Switchgear cable current transformer Features

  • According to IEC / EN 61869-1 and -2 / VDE 0414-9-1 and -2
  • Designed asring-core current transformer, 3-pole
  • Free ofdielectrically stressed cast-resin parts (due to design)
  •     Insulationclass E
  • Inductive type
  • Climate-independent
  • Secondary connectionby means of a terminal strip in the panel.

Installation

  • Mounting location:– For individual panels type R(500) and L(500) (optional)– Arranged outside the switchgear vessel on the bushings of the cable connection– Factory-assembled.

Siemens 8DJH Switchgear cable current transformer Further designs(option)
For protection equipment   based on the current-trans- former operation principle:

  • Protection system7SJ45 as definite-time overcurrent    protection
  • Definite-time overcurrentprotection relay,make Woodward / SEG, type WIP 1
  • Definite-time overcurrent protection relay,make Woodward / SEG, type WIC.
 

Siemens 8DJH Switchgear cable current transformer Bus / cable-type current transformer:

  • According to IEC / EN 61869-1 and -2 / VDE 0414-9-1 and -2
  • Designed asring-core current transformer, 1-pole
  • Free ofdielectrically stressed cast-resin parts (due to design)
  • Insulationclass E
  • Inductive type
  • Secondary connectionby means of a terminal strip in the panel.

Installation

  • Siemens 8DJH Switchgear cable current transformer Mounting location:– Arranged outside the switchgear vessel on the screened busbar section in bus sectionalizer panels with switch-disconnector type S and bus sectionalizer panels with circuit-breaker   type V with the option of busbar current transformers– Arranged outside the switchgear vessel around the cable at the panel connection for 310 mm panel width (cable feeders  type 8DJH-R and K), transformers mounted on a supporting    plate at the factory;final assembly around the cables on site.