Categories
Categories

What is the external structure of the Siemens 8DJH switchgear?

Apr 19th,2024 471 Views


1 Wiring duct, low-voltage compartment

  • Metallic wiring duct (option) on the switchgear for panel-overlapping secondary wiring
  • Alternatively, low-voltage compartments (option) in different heights of 200 mm, 400 mm, 600 mm,

  or 900 mm for customer-specific secondary equipment

2 Busbar extension, modularity

  • Busbar extension as an ordering option
  • Plug-in unit consisting of contact coupling and screened silicone coupling
  • Insensitive to pollution and condensation
  • 8DJH-Switchgear installation, extension, or panel replacement without gas work

3 Indicators

  • Voltage detecting systems, short-circuit / earth-fault indicators and transformer monitors from various manu facturers

4 Ring-main feeder

  • Switching functions as general-purpose switch-disconnector according to IEC 62271-103 and IEC 62271-102
  • Designed as a three-position switch incorporating the functions of a switch-disconnector and a make-proof earthing switch
  • Switch positions: CLOSED – OPEN – EARTHED
  • Manual operating mechanism, optionally motor operating mechanism

5 Transformer feeder

  • High-voltage switch-fuse combination according to IEC 62271-105
  • Designed as a three-position switch
  • 8DJH-Switch positions: CLOSED – OPEN – EARTHED
  • Manual operating mechanism, optionally motor operating mechanism
  • Mechanical “fuse tripped” indicator at the switchgear front

6 HV HRC fuse assembly

  • Fuse boxes, 1-pole, below the switchgear vessel
  • Fuse slide for easy replacement of HV HRC fuses without tools
  • HV HRC fuse-links according to DIN 43625 (main dimensions) with striker in “medium” version according to IEC 60282-1, for short-circuit protection of transformers

7 SiBushing

  • Outside-cone bushing type C with integrated sensors for current, voltage, and temperature measuring (option)

8 Cable compartment

  • Bushings according to DIN EN 50181 with outside cone and bolted connection M16 as interface type C (standard in cable, ring-main, and circuit-breaker feeders) or with outside cone and plug-in contact as interface type A (standard in transformer feeders)
  • Adjustable cable bracket with C-rail, optionally with plastic cable clamps pre-assembled at the factory

Connection of:

  • Cable elbow plugs or cable T-plugs
  • Thermoplastic-insulated cables (1- and 3-core cables)
  • Ring-core current transformers according to IEC 61869-1 and -2, around the cables
  • Current sensors according to IEC 61869-10, around the cable plugs or around the cables
  • Voltage sensors (resistor divider) according to IEC 61869-11, mounted on the cable plugs
  • Surge arresters

9 Enclosure

  • Hermetically tight, welded switchgear vessel made of stainless steel
  • Enclosure made of sendzimir-galvanized sheet steel, switchgear front powder-coated

10 Dimension options

  • 8DJH Switchgear height 1400 mm (optionally 1040 mm, 1200 mm or 1700 mm)
  • Deep cable compartment cover

11 Pressure relief

  • Pressure relief downwards
  • For further pressure relief versions, see page 34
  • Up to IAC A FL 21 kA/ 1 s or IAC A FLR 21 kA/ 1 s